Job Name Location
Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #
Cooling (Btu/h)
Heating (Btu/h)
Voltage
ø/V/Hz
Type
Output (W)
H/M/L
Standard "WC
Min. / Max. "WC
Liquid (flare) Inches
Suction (flare) Inches
rain IQFKHVDrain
W X H X D Inches
WHLJKW
Supply
Return,'
Sound Level H / 0LdB
Specifications
Performance
Nominal Capacity
External Static
Pressure
Motor
Power
Nominal Running Current (A)
Filter Box
Unit
Dimensions
Duct Connections
(inches)
Safety Certifications
Nominal cooling capacities are based on: Indoor temperature: 80 ͼF DB, 67ͼF WB. Outdoor temperature: 95ͼF DB, 75ͼF WB.
Nominal heating capacities are based on: Indoor temperature: 70 ͼF DB, 60ͼF WB. Outdoor temperature: 47ͼF DB, 43ͼF WB.
Samsung and Quietside maintains a policy of ongoing development, specifications are subject to change without notice.
Fan
Accessories
Condensate Pump
Piping
Connections
External Contact Control
Wireless Receiver Kit
Type
Refrigerant
Type
Control Method
• Compatible with Samsung DVM S and Mini DVM systems:
AM***FXVA*R/AA, AM***FXVA*H/AA, AM0**FXMDCH/AA only.
• High-voltage terminal block temperature sensor to disable unit in
the event overheating of power connection.
• Discharge air temperature sensor with target discharge
temperature control capability (consult technical data books or
Quietside Corporation for full details)
Construction
The unit shall be constructed of insulated, galvanized steel
Heat Exchanger
The heat exchanger shall be mechanically bonded fin to copper
tube
Indoor Fan
Indoor fan is a twin, backward curved centrifugal type with a single
fan motor
Three fan speed settings and auto setting
Controls
The unit shall be operated via a wireless or wired remote control
with DDC type signal
The unit shall integrate with the Samsung NASA Controls Network
Solution
Controls shall integrate with a BMS system
Control wiring shall be 2 X 16 AWG shielded wire
Air Filtration
The unit does not include an air filter as standard
Filtration is field provided/installed
Pressure drop across the filter must be factored into the total ESP.
OEV
&)08/
$LUIORZ
&RQGHQVDWH
3LQWV+RXU
SUBMITTAL
Page
www.SamsungDVM-S.com
888-699-6067
AM018FNMDCH/AA
1of2
Samsung DVM S Series, MSP (Medium Static) Ducted Unit
18,000 (13,800 SH)
20,000
4.86
1 / 208-230 / 60
1.4
Sirocco (2)
Non Feedback SSR (1)
124
512 / 459 / 406
0.157
0 - 0.315
R410A
Electronic Expansion Valve
1/4
1/2
OD 1 1/4, ID 1
35 7/16 X 10 1/4 X 18 7/8
64
33 1/4 X 7 9/32
27 1/2 X 6 1/4
35 / 33 / 31
MDP-M075SGU3D
FB-M1824
MIM-B14
MRK-A10N
ETL
& ETLc
QS-DVMS-042014A