Control Systems
128
9,9,
Building management system
Click ‘Object ID’ from the ‘Object ID’ column.
Detail information window will appear and detail information will be displayed.
Ex)
Indoor Unit
DNET (Gateway number) : 9
Indoor Unit Address: 01.01.32
Device ID: 941732
Item DNET-Range [Digit 2] CPP-Range [Digit 3] INDOOR-Range [Digit 2]
On/Off controller 1~40 000~015 64
SIM / PIM 1~40 100~115 64
DMS2 DI/DO 1~40 300~315 64
Interface module
(Outdoor unit)
1~40 400~655 (16 x 16) 64
Indoor Unit/ERV/AHU kit 1~40 400~655 0~63
Gateway 1~40 900 64
Device Instance Number (Gateway ID) Indoor unit main address
9 417 32
On/Off controller address Interface module address
400 + 1 x 16 + 1 = 417
2. BACnet Gateway
6) Description of device ID
󰞃 MIM-B17N
Checking device ID from BACnet Gateway