Outdoor units
9
Pipe length(m)
Height difference (m)
20
10
15
0
5
-10
-5
-15
-20
20
15
0 5 10 25
100% 100% 100%
95%
30
20
10
15
0
5
-10
-5
-15
-20
20
15
0 5 10 25
100% 90%
88%
30
95%
Pipe length(m)
Height difference (m)
9-1. Capacity correction
19) RC071SHXEA
(1) Cooling
(2) Heating
Pipe length(m)
Height difference (m)
30
25
20
10
15
0
5
-10
-5
-20
-25
-15
-30
20
15
0 5 10 25 30 35 4540
100%
50
98% 89%95% 92%
30
25
20
10
15
0
5
-10
-5
-20
-25
-15
-30
20
15
0 5 10 25 30 35 4540
100%
80%
50
85%90%
Pipe length(m)
Height difference (m)
21) RC100SHXEA
(1) Cooling
(2) Heating
20) RC090SHXEA
(1) Cooling
Pipe length(m)
Height difference (m)
(2) Heating
Pipe length(m)
Height difference (m)
30
25
20
10
15
0
5
-10
-5
-20
-25
-15
-30
20
15
0 5 10 25 30 35 4540
100%
99% 90%95%
50
92%
30
25
20
10
15
0
5
-10
-5
-20
-25
-15
-30
20
15
0 5 10 25 30 35 4540
100%
90%
50
94%96%