Indoor outlet pipe Connecting pipe
Flare nut
5. Check if you ared the pipe correctly (see examples of incorrectly ared pipes below).
6. Align the pipes to connect them easily. Tighten the are nuts rst with your hands, and then with a torque wrench,
applying the following torque:
7. For further details on how to connect to the outdoor unit and purge the air, refer to the installation manual supplied
with the outdoor unit
Correct
Uneven
Thickness
Cracked
Damaged
Surface
Inclined
• Excessivetorquecanbecauseofgasleakage.Incasebrazingthepipe,thenitrogengasmustbeblownintothe
pipe (50 Pa). The joint must be accessible and serviceable.
• Tightenthearenutwithtorquewrenchaccordingtospeciedmethod.
If theare nut is over-tightened, theare may break and cause refrigerant gas leakage.
4. Put a are nut slightly into the pipe and modify theare.
Outer Diameter (D) Depth (A) Flaring Size (B)
ø6.35 mm 1.3 mm 8.7 - 9.1 mm
ø9.52 mm 1.8 mm 12.8 - 13.2 mm
ø12.70 mm 2.0 mm 16.2 - 16.6 mm
ø22.23 mm 2.2 mm 19.3 - 19.7 mm
Pipe Flare
90°± 2°
°
2
±°
5
4
R 0.4~0.8
B
Outer Diameter
Torque
N•m kgf•cm
ø6.35 mm 14~18 140~180
ø9.52 mm 34~42 350~430
ø12.70 mm 49~61 500~620
ø15.88 mm 68~82 690~830
Cutting or extending the pipe
English-39
INSTALLATION05