E-42
Channel Setting by Indoor Unit
1
Click [EHP Power Consumption Inspection] [Channel
setting by indoor unit] when DMS2 web page menu screen
appears.
2
Click [Edit] when the setting channel by indoor unit screen
appears.
3
Check the address and channel information of SIM/PIM which
is connected to
watt-hour meter.
If 0~7 SIM/PIM units execute tracking, it will be displayed
as 16~23 in DMS2.
Below table shows the channel information of the terminal
which SIM and
watt-hour meter is connected. (Terminal block 1 is on the
most left side in SIM.)
PIM: Channel 1 is on the most left side and 8 channels are
arranged in a line.
When doing power distribution, set SIM/PIM channel for
each indoor unit.
Terminal block
Location
Terminal
block 1
Terminal
block 2
Terminal
block 3
Terminal
block 4
Top part 1 2 3 4
Bottom part 5 6 7 8
Setting the Power Distribution