
E-98
Description
1. Remote control restriction status
2. Filter alert status
3. Thermo On/Off status
4. Error alert Status
SNVT Type
SNVT_state: 16 Unsigned Bitfields
Value and operation
Byte Bit9 Bit8 Operation Remark
Flags_1
0 0 Unlock
nvoUserLockout0 1 Level1
1 0 Lock
Byte Bit value Operation Remark
Flags_2
2
0 No alarm
nvoFilterAlarm
1 Alarm
1
0 Thermo Off
Thermo On/Off
1 Thermo On
0
0 No Error
nvoErrorCode
1 Error
nvoDeviceAlarm(18)
Description
Operation Mode restriction
SNVT Type
SNVT_switch: Unsigned/singed Short
Value and operation
Value State
Unlock 0.0 0
Cool only 1.0 1
Heat only 2.0 1
nvoOccOpMode(19), nviOccOpModeCmd(8)
Description
Setting/monitoring Lower limit temperature
and function toggle
SNVT Type
SNVT_switch: Unsigned/singed Short
Value and operation
Operation Value State
Unlock 18.0 ~ 30.0 0
Lock 18.0 ~ 30.0 1
Cool: 18.0°C ~ 30.0°C
nvoCoolTempLock(20), nviCoolTempLock(9)
LonWorks Gateway Setting (Continued)
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 98 2015-06-18 오후 5:34:30
Komentarze do niniejszej Instrukcji