Samsung AVXTJ series Przewodnik Instalacji Strona 7

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 137
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 6
Installation guide
7
3. DVM design process
DVM is a multi-system air conditioner that changes its performance by different conditions such as design
temperature
, indoor and outdoor unit combination rates, heating operation rates, piping length, and
level difference.
It is important to select the appropriate design condition to the load specification of
each room.
Design temperature
Calculate cooling and heating loads
Power supply, piping length and level difference
Consider design temperature conditions to select
larger indoor types than actual load.
Determine outdoor units by the sum of the capacity
of preliminary selected indoor units: At this time,
decide how much combination ratio to permit.
Calculate actual capacity of
outdoor units considering
design temperature, indoor
and outdoor unit combination
ratio, piping length, level
difference, heating operation
rates, etc.
Calculate actual capacity of each indoor
unit based on the calculated outdoor
capacity.
If Indoor unitsactual capacity is lower than the load,
reselect ones with a larger capacity. Depending on
designersown discretion.
If there is no indoor unit with a larger capacity, add
another indoor unit.
Przeglądanie stron 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 136 137

Komentarze do niniejszej Instrukcji

Brak uwag