Main Function
Zone Management
S-NET mini can control indoor units conveniently by using zone management
system.
Zone/Indoor name can be maximum 32 letters long.
Special character or symbols (\, /, ;, *, ?, “, “, ‘, ’, <, >) cannot be used in a name.
Each zone can contain maximum 64 indoor units.
Security Setup
To maintain security, you can set password on your S-NET mini.
Password Enabled: You will need to enter the password to use the menu with
the Lock ( ) icon.
Password Disabled: You may use all the function in the main menu without any
restrictions.
View DVM Information
You can check error log, connection status and cycle status.
S-NET mini saves maximum 256 error logs. If the number of errors exceeds 256,
only the latest 256 cases are stored by deleting the oldest error history.
You can check device name, IP address, date of occurrence, current status, date
resolved, and type of error from the error log.
Device
Type of an error
Indoor unit
Indoor unit communication error
Indoor unit sensor related error
Other errors
Outdoor unit
Outdoor unit communication error
Piping inspection error
Outdoor unit sensor related error
Other outdoor unit related errors
Solution Products such as the Centralized Controller
Solution device related communication error
PEAK Power Management
S-NET mini can manage and monitor PEAK power through DMS that is
connected to a PEAK transmitter.
PEAK power management
In case of temporary power usage reaching the PEAK power, the air conditioner
restricts its use, such as changing its mode to Fan mode or cutting off the
power, to minimize the power usage.
S-Net mini controls and manages indoor units according to the alarm level
provided by DMS to maintain the PEAK power.
PEAK level is composed of 4 different levels from 0~3, and the DMS, connected
to a PEAK control interface module, provide the PEAK level information.