Main Function
Indoor unit usage restriction
S-NET mini should have DMS in connection with the PEAK control transmitter.
When the indoor unit is operating in Dry/Cool/Auto, they will switch to
Fan mode while PEAK power management is applied.
When the indoor unit is operating in Heat mode, it will switch to ‘Fan mode’,
‘Power off’ or ‘Change set temperature(16ºC)’. (You can change these setting on
S-NET mini.)
If the indoor unit with its power off has been assigned to PEAK power
management group and the user try to operate the indoor unit while PEAK
power management is in active, indoor unit will automatically stop its operation.
If the indoor unit operating in Fan mode has been assigned to PEAK power
management group and the user try to change operation mode to Cool or Heat
mode while in PEAK power management is in active, indoor unit will
automatically switch its mode to Fan mode.
In PEAK power management mode, ‘Turning on the indoor unit’ or ‘Changing
operation mode to Cool/Auto/Dry’ will be restricted.
In PEAK power management mode, ‘Turning on the indoor unit’ or ‘Changing
operation mode to Cool/Auto/Dry’ within the schedule and all the other events
will be ignored.
‘Turning on the indoor unit’ or ‘Changing operation mode to Cool/Auto/Dry’
through Centralized controller or Wired/Wireless remote controller while in PEAK
power management mode will automatically turn off the indoor unit or switch
its operation mode to Fan mode.
In PEAK power management mode, if the user turns off the indoor unit within
PEAK power management group, it will remain off after PEAK power
management has been deactivated.
Others
Be aware that the indoor units in PEAK power management mode will not return
to its previous settings if Tracking occurs in PEAK power management mode.
Date/Time changes will not affect the Circulation control period if the changes
has been made in PEAK power management mode.
Power monitoring
Power monitoring is an operation mode which monitors maximum power and
the current power usage.
Target Demand: This is the maximum amount of power set by user.
Current Target Power Demand: This is the amount of power left before reaching
the Target Demand.
Current Power: This is current power usage in kW unit.
Current Demand Power: This is the accumulated demand power from starting
period.