OWNER’S GUIDE  CONDITIONERS, DAQ | 13329
Part 2: Basic Sensor Test
Bridge Sensor: It is checked if the supply current doesn’t exceed the maximum value, and if the excitation voltage is within the
predefined value.
DAQP-STG Full bridge signal connection
6-wire and 4-wire sensor connection
Voltage or Current excitation are allowed.
Sense lines MUST be connected to the excitation also when 4-wire connection is used.
6-wire sensor connection: Sense+ is connected to EXC+ at the sensor
4-wire sensor connection: Sense+ is connected to EXC+ at the connector
DAQP-STG Half bridge signal connection
5-wire and 3-wire sensor connection, and potentiometric sensors
5-wire sensor connection: Sense+ is connected to EXC+ at the sensor
3-wire sensor connection: Sense+ is connected to EXC+ at the connector
Voltage or Current excitation are allowed.